Modbus TCP
Home > Products > Horizontal I/O> Modbus TCP > UH-MT-D16C16P
Product search
Product Catalog


1, The digital input module has 16 channels and the digital output module has 16 channels.
2, Support source type or leakage type input, input PNP type high level is effective or NPN type low level is effective.
3, Support digital source type output, PNP type high level effective.
4, It can receive field side (such as: sensor, encoder, switch or proximity switch) binary control signal.
5, The module adopts Push-in CAGE CLAMP technology, allowing a single strand of wire to be inserted directly.
6, Support 01/02/03/04/05/06/15/16 and other function code communication.
2, Support source type or leakage type input, input PNP type high level is effective or NPN type low level is effective.
3, Support digital source type output, PNP type high level effective.
4, It can receive field side (such as: sensor, encoder, switch or proximity switch) binary control signal.
5, The module adopts Push-in CAGE CLAMP technology, allowing a single strand of wire to be inserted directly.
6, Support 01/02/03/04/05/06/15/16 and other function code communication.
Digital input/output hybrid parameters | ||
Type | UH-MT-D16C16P | |
Input parameter | ||
Number of channels | 16 | |
Signal type | NPN & PNP | |
"ON" signal voltage (PNP) | 15V - 30V | |
"OFF" signal voltage (PNP) | -3V - 3V | |
"ON" signal voltage (NPN) | -3V - 3V | |
"OFF" signal voltage (NPN) | 15V - 30V | |
Connection type | 1 - Wire system | |
Reverse circuit protection | Yes | |
Isolation mode | Optical isolation from the field layer | |
Error diagnosis | Yes | |
Typical input current | 3mA | |
The maximum crimp area of the wire | 1.5mm² | |
Maximum crimp area of conductor (AWG) | AWG16 | |
The minimum crimp area of the wire | 0.34mm² | |
Minimum crimp area of conductor (AWG) | AWG22 | |
Strip length | 8-10mm | |
Output parameter | ||
Number of channels | 16 | |
Signal type | PNP | |
"ON" signal voltage | DC 24V (±25%) | |
"OFF" signal voltage | DC 0V (±3%) | |
Connection type | 1 - Wire system | |
Reverse circuit protection | Yes | |
Isolation mode | Optical isolation from the field layer | |
Error diagnosis | Yes | |
The maximum crimp area of the wire | 1.5mm² | |
Maximum crimp area of conductor (AWG) | AWG16 | |
The minimum crimp area of the wire | 0.34mm² | |
Minimum crimp area of conductor (AWG) | AWG22 | |
Strip length | 8-10mm | |
Communication parameter | ||
Communication protocol | Modbus TCP | |
Transmission rate | 100Mbps | |
Communication distance | ≤100 m(Distance between stations) | |
Station type | Remote I/O station | |
Occupied work station | 1 station | |
Address setting | Modbus TCP specifications | |
Topological structure | Bus topology | |
Isolation mode | Electrical isolation from field floor | |
Transmission medium | Ethernet CAT5 cables | |
Power supply parameter | ||
Connection mode | PUSH-IN terminal | |
Operating voltage | 24V DC +20%/-15% | |
System feed current | <150mA | |
The maximum crimp area of the wire | 1.5mm² | |
Maximum crimp area of conductor (AWG) | AWG16 | |
The minimum crimp area of the wire | 0.34mm² | |
Minimum crimp area of conductor (AWG) | AWG22 | |
Strip length | 8-10mm | |
Basic parameter | ||
Class of protection | IP20 | |
Overall dimensions (H x W x D) | 43.7 mm X 100 mm X 100 mm | |
Operating temperature | -10 ~ 55°C | |
Storage temperature | -20 ~ 85°C | |
Relative humidity | 5 ~ 95% RH (non-condensing) | |
Authentication | CE | |
Altitude | Below 2000 m (80kPa) | |
Pollution level | Level 2 | |
Immunity to interference | Power cable 2kV (IEC 61000-4-4) | |
Overvoltage class | II | |
EMC anti-interference level | Zone B,IEC61131-2 | |
Vibration resistance | IEC 60068-2-6 | |
5Hz ~ 8.4Hz, amplitude 3.5mm, 8.4Hz ~ 150Hz, acceleration 9.8m /s², X, Y, Z | ||
100 minutes in each direction (10 times, 10 minutes each, 100 minutes in total) | ||
Impact resistance | IEC 60068-2-27, 9.8m/s², 11ms, X/Y/Z, 3 times each in 3 axes and 6 directions | |
LED status | ||
PWR | On: The power supply to the module is normal | |
Off: The power supply to the module is abnormal | ||
RUN | On: The system is running properly | |
Off: The system is not running properly | ||
PORT1 | Blinking: Data is available on the network | |
PORT2 | Blinking: Data is available on the network | |
Channel light | On: The signal of the corresponding channel is valid | |
Off: The signal of the corresponding channel is invalid | ||
Ps | On: The power supply to the system is normal | |
Off: The system power supply is abnormal | ||
Pf | On: The onsite power supply is normal | |
Off: The onsite power supply is abnormal |